Products

Load Break Switches

ABB OT1250E03P SWITCH-DISCONNECTOR OT1250E03P

Product Code: OT1250E03P

3-pole, front operated, base mounted switch-diconnector with black IP65 handle and shaft, terminal bolt kit included

Technical Specifications

Impulse Withstand Voltage (kV/1.2µS) 12
Brand ABB
Cable Cross Section (mm²) 2 x 400
Control Element Colour Black
Conventional Free-Air Thermal Current - Ith (A) 1250
Conventional Thermal Current - Ithe (A) 1250
Degree of Protection - Handle IP65
Dimensions (mm) 334.5W x 306H x 145.5D
Handle Colour Black
Handle Dimensions (mm) 308.7W x 70H x 69.4D
Handle Length (mm) 274
Handle Material Plastic
Handle Type Pistol
Icw (kA/1s) - Short-time Withstand Current Rating 50
Included Handle, Shaft
Interlockable Yes
Main Circuit Electrical Connection Bolt Connection
Maximum Operational Voltage AC (V) 1000
Mode of Operation Front operated
Mounting Type Base Mount
NEMA Degree of Protection 1
No. of Poles 3
Operating Mechanism Mechanism at the End of the Switch 03 (Left Side)
Operational Current AC-22A @ 380-415V (A) 1250
Operational Current AC-22A @ 500V (A) 1250
Operational Current AC-22A @ 690V (A) 1250
Operational Current AC-23A @ 380-415V (A) 1250
Operational Current AC-23A @ 500V (A) 1250
Operational Current AC-23A @ 690V (A) 1250
Operational Power AC-23A @ 400-415V (kW) 710
Operational Power AC-23A @ 500V (kW) 900
Operational Power AC-23A @ 690V (kW) 1200
Poles 3P
Pollution Degree 3
Position of Mechanism Mechanism at the End of Switch 03 (Left Side)
Position of Operation Front Operated
Power Loss (W) 29/Pole
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage (V) 1000
Rated Operational Current AC-21A 415V (A) 1250
Rated Operational Current AC-22A 380-415V (A) 1250
Rated Operational Current AC-22A 500V (A) 1250
Rated Operational Current AC-22A 690V (A) 1250
Rated Operational Current AC-23A 380-415V (A) 1250
Rated Operational Current AC-23A 500V (A) 1250
Rated Operational Current AC-23A 690V (A) 1250
Rated Operational Power AC-23A 380-415V (kW) 710
Rated Operational Power AC-23A 400-415 V (kW) 710
Rated Operational Power AC-23A 500V (kW) 900
Rated Operational Power AC-23A 690V (kW) 1200
Rated Operational Voltage (V) 1000
Rated Short-Time Withstand Current - Icw (kA) 50
Rated Short-time Withstand Current - Icw (kA/1s) 50
Rated Uninterrupted Current - Iu (A) 1250
Shaft Dimensions (mm) 12W x 12H x 280D
Sizes (mm) 334.5W x 306H x 145.5D
Standards and Approvals IEC 60947-3
Suitable For Distribution Board Installation
Terminal Type Lug terminals
Terminal Width (mm) 50
Type Main Switch
Type of Handle Pistol
Type of Mounting Base Mount
Voltage (V) 1000

Documents

Products to compare:
Comparing Products