Products

Load Break Switches

ABB OT400ES03 SWITCH-DISCONNECTOR OT400ES03

Product Code: OT400ES03

3-pole, side operated, base mounted switch-diconnector, handle and shaft are not included, terminal bolt kit included

Technical Specifications

Impulse Withstand Voltage (kV/1.2µS) 12
Brand ABB
Conventional Free-Air Thermal Current - Ith (A) 400
Conventional Thermal Current - Ithe (A) 400
Degree of Protection - Handle IP65
Dimensions (mm) 226W x 185H x 107D
Icw (kA/1s) - Short-time Withstand Current Rating 15
Main Circuit Electrical Connection Bolt Connection
Maximum Operational Voltage AC (V) 1000
Mode of Operation Side Operated
Mounting Type Base Mount
NEMA Degree of Protection 1
No. of Poles 3
Operating Mechanism Mechanism at the End of the Switch 03 (Left Side)
Operational Current AC-22A @ 380-415V (A) 400
Operational Current AC-22A @ 500V (A) 400
Operational Current AC-22A @ 690V (A) 400
Operational Current AC-23A @ 380-415V (A) 400
Operational Current AC-23A @ 500V (A) 400
Operational Current AC-23A @ 690V (A) 400
Operational Power AC-23A @ 400-415V (kW) 230
Operational Power AC-23A @ 500V (kW) 280
Operational Power AC-23A @ 690V (kW) 400
Poles 3P
Pollution Degree 3
Position of Mechanism Mechanism at the End of Switch 03 (Left Side)
Position of Operation Side Operated
Power Loss (W) 10/Pole
Rated Impulse Withstand Voltage (kV) 12
Rated Insulation Voltage (V) 1000
Rated Operational Current AC-21A 415V (A) 400
Rated Operational Current AC-22A 380-415V (A) 400
Rated Operational Current AC-22A 500V (A) 400
Rated Operational Current AC-22A 690V (A) 400
Rated Operational Current AC-23A 380-415V (A) 400
Rated Operational Current AC-23A 500V (A) 400
Rated Operational Current AC-23A 690V (A) 400
Rated Operational Power AC-23A 380-415V (kW) 230
Rated Operational Power AC-23A 400-415 V (kW) 230
Rated Operational Power AC-23A 500V (kW) 280
Rated Operational Power AC-23A 690V (kW) 400
Rated Operational Voltage (V) 1000
Rated Short-Time Withstand Current - Icw (kA) 15
Rated Short-time Withstand Current - Icw (kA/1s) 15
Rated Uninterrupted Current - Iu (A) 400
Sizes (mm) 226W x 185H x 107D
Standards and Approvals IEC 60947-3
Suitable For Distribution Board Installation
Terminal Type Lug terminals
Type Main Switch
Type of Mounting Base Mount
Voltage (V) 1000

Documents

Products to compare:
Comparing Products