  • SW LOAD BREAK 200A 3P 1000V 0

SW LOAD BREAK 200A 3P 1000V 0

Product Code: OT200E03WP

Technical Specifications

Mechanical Durability 20000
Rated Insulation Voltage acc. to IEC/EN 60664-1 1000 V
Rated Making Capacity AC-3 (690 V) 30 kA
Rated Operational Current AC-21A (A) (380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A (1000 V) 200 A
Rated Operational Current AC-22A (A) (380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-23A (A) (380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Power AC-23A (kW) (220 ... 240 V) 60 kW (400 ... 415 V) 110 kW (500 V) 132 kW (690 V) 200 kW
Rated Short-time Withstand Current Low Voltage - Icw (A) for 1 s 8 kA
Remove Yes
Brand ABB
Conventional Free-Air Thermal Current - Ith (A) T = 40 °C 200 A
Conventional Thermal Current - Ithe (A) Fully Enclosed 200 A
Degree of Protection Front IP00
Dimensions (mm) 150 * 169.5 * 82.5 [H*W*D]
Handle Colour Black
Handle Type Handle and shaft included
Lock Type Yes
No. of Poles 3
Operating Mechanism Front operated
Pollution Degree 3
Position of Line Terminals Top In - Bottom Out Bottom In - Top Out
Power Loss (W) at Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current - Inc (kA) (315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (kV) 12
Rated Operational Voltage AC (V) Main Circuit 1000V
Standards IEC 60947-3
Switching Type Mechanism at the End of the Switch 03 (Left Side)
Terminal Type Lug terminals
Terminal Width (mm) 20 mm
Tightening Torque (Nm) acc. IEC 60947-1 15 … 22 N·m
Type of Mounting Base mounting

Documents

Products to compare:
Comparing Products